The soft starter allows the user to apply adjustable voltage to the motor, in order to reduce the current, and to gradually ramp up to full voltage and speed for a soft start, and conversely allows the user to gradually ramp down for a soft stop. Suitable for use on any application that requires a soft start. At full voltage it runs at 15kW with an armature current of 30A.
|
Motor Power |
15kW |
Rated Current |
30A |
Control System |
Thyristor control in all 3
phases |
Wiring Connection |
If line or in delta |
Current Limit |
100-800% of motor rating |
Starting Torque
|
10-90% of direct on line |
Stopping |
Ramp, coast or DC injection
by external unit |
DC Injection Braking |
DC injection by external unit |
Accel/Decel |
1-99s linear or pump control |
Bypass |
Control of external bypass
contactor |
Frequency range |
45 to 65Hz |
Input Terminals |
2 fixed and 2 programmable |
Output Relay |
2 programmable relays |
Overload |
Electronic adjustable |
Protection |
20 functions inc- Stalled rotor |
Trip History |
Last 5 trips |
Set-up |
Quick application list or advanced
parameters |
| Energy saving |
Energy optimisation built-in |
| Interface |
Simple switches, or optional digital 2 line LCD
display keypad |
| Enclosure |
IP20 size 1 & 2, IP00 above |
| International Standards |
UL. C-UL (CSA), CE and C-Tick - Complise with EMC
& LV Directives |
Click here for a manual.
|