16A Three phase line choke, with an inductance of 1.84mH.
Connected in the mains supply to the inverter. This will help to reduce harmonics that are caused when the mains is rectified to create a DC link. They will also reduce the peak currents drawn by the inverter or other device. They also help to protect the input rectifier from some mains problems. Harmonics can cause premature failure of input rectifiers and phase correction capacitors.
|
General |
| Maximum Power Loss |
PV |
W |
44 |
Standards |
|
|
IEC/EN 61558-2-20-2000,
VDE 0570 Part 2-20/04-2001, UL, CSA |
Operating Temperature |
|
°C |
-25/+40, up to 70 with current derating
|
Storage Temperature |
|
°C |
–25...+85 |
Shock Resistance |
|
|
11 ms2/15 g, 3 impacts |
Vibration Resistance |
|
g |
1 (at 0 – 150 Hz) |
Vibration |
|
|
0.35 mm at 10 – 55 Hz |
Pollution Degree |
|
|
1 (VDE 0160) |
Altitude |
|
m |
0 to 1000 above sea level, up to 5000
with current derating (see notes) |
Mounting Position |
|
|
Standing vertically, suspended horizontally
|
Free Surrounding Areas |
|
|
< 50 |
Degree of Protection (terminals) |
|
|
IP20 up to 40A
IP00 up to 50A
|
Rated Duty Factor |
|
% DF |
100 |
Overload Cycle |
|
|
1.5 × Ie for 60 s every 600 s |
Weight |
|
kg |
2.9 |
| Electrical data |
Rated Voltage |
Ue |
V AC |
400 |
Max. Supply Voltage |
UL |
V AC |
550 ±0% |
Operating Frequency |
f |
Hz |
50/60 |
Insulation Class |
|
|
B |
|
Electrical Connection |
Terminations |
|
|
• (40A) |
Connection Lugs |
|
|
• (50A) |
|