260A Three phase motor choke, with an inductance of 0.15mH.
Connected in the inverter output circuit between the inverter and the motor. This will help to reduce reflected waves, often caused by long or multiple motor cables. Reflected waves can damage the inverter output devices and cause greater RFI (radio frequency interference), this may cause any RFI filter fitted to be damaged. Motor chokes are recommended for all inverter application, regardless of motor cable length, for motor cable lengths of 30m or more motor chokes should be very seriously considered.
|
General |
| Maximum Power Loss |
PV |
W |
520 |
Standards |
|
|
IEC/EN 61558-2-20-2000,
VDE 0570 Part 2-20/04-2001, UL, CSA |
Operating Temperature |
|
°C |
-25/+40, up to 70 with current derating
|
Storage Temperature |
|
°C |
–25...+85 |
Shock Resistance |
|
|
11 ms2/15 g, 3 impacts |
Vibration Resistance |
|
g |
1 (at 0 – 150 Hz) |
Vibration |
|
|
0.35 mm at 10 – 55 Hz |
Pollution Degree |
|
|
1 (VDE 0160) |
Altitude |
|
m |
0 to 1000 above sea level, up to 5000
with current derating (see notes) |
Mounting Position |
|
|
Standing vertically, suspended horizontally
|
Free Surrounding Areas |
|
|
< 50 |
Degree of Protection (terminals) |
|
|
IP20 up to 50A
IP00 from 63A
|
Rated Duty Factor |
|
% DF |
100 |
Overload Cycle |
|
|
1.5 × Ie for 60 s every 600s (<24A)
1.2 × Ie for 60 s every 600s (>24A) |
Weight |
|
kg |
45 |
| Electrical data |
Rated Voltage |
Ue |
V AC |
400 |
Max. Supply Voltage |
UL |
V AC |
750 ±0% |
Operating Frequency |
f |
Hz |
0...200 |
Insulation Class |
|
|
B (100A) F (150A) |
|
Electrical Connection |
Terminations |
|
|
• (50A) |
Connection Lugs |
|
|
• (60A) |
|